HOME : Back -> Pro Audio -> Redback Solutions -> Redback

Redback Emergency/Fire Evacuation Control Panel - 1U 19" Rackmount, 240V/24V DC

Product May Vary From Image
Part No:
104328
Brand:
Manuf No:
A2075A
Usually Ships:
No Longer Available   More info

Ship Weight:
2.5 KG  Details
Product Description
This simple to operate controller is designed around industry standard building emergency alert/evacuate requirements. When connected to a paging system amplifier, building occupants can be alerted and/or evacuated in an orderly manner in the event of an emergency Eg: fire, gas leak, bomb scare, earthquake and so forth. Auto or manual modes of operation are selected by the front panel keyswitch.

Modes of operation:
Auto The alert tone is generated when a signal is received from the fire indicator board (FIB). After a preset time the evacuate tone is sounded unless the alert tone is manually reset. The evacuation tone continues until manually reset. When selected to auto, front panel alert and evac controls are inoperative. Other controls such as paging, bell chime and BGM function normally.
Manual In the manual position any of the functions may be initiated from the controls on the front panel, i.e. Alert, Evac, or PA.
Remote cancel function Terminals are provided for the connection of a remote cancel switch. When activated with a closing set of contacts this will cancel any activated tone, regardless of the position of the master auto/manual/isolate keyswitch on the front panel. This is particularly useful when the main equipment may not be readily accessible.
Other functions Provision has been made for a BGM source to be played through the controller. BGM is automatically muted when any other function is operated. A microphone input has been included on the front panel. This can be used for either general or emergency paging. Paging overrides all other functions. A pre-announcement chime is available on the microphone input. This can be switched on or off internally as preferred. Included is a unique tone or bell chime for signalling lunch breaks, start of class etc. This can be operated from the front panel or via contacts on the rear panel for remote activation ie. by a time clock or remote switch.

Features:
1U 19" rack mount
Interfaces with fire indicator boards
Remote operation of alert and evac tones
240V mains and 24V DC operation
Auto / manual / isolate 003 key switch
Local operation of alert, evac, PA
Provision for voice-over message
Microphone socket for PA use
BGM and auxiliary input
Bell chime facility
Switched 24V output for operating override relay on remote volume controls with alert/evac/PA signals
Separate relays for alert and evac signals for external strobe light operation
On-board timer for remote alert activation adjustable from 30 seconds to 7.5 min in 30 second increments
Externally operated inputs are activated by switching to ground
Auxiliary level output
Can be used in a standard PA system
10 year warranty

Specifications
Output Level: 0dBm
Distortion: 0.01%
Frequency Response: 140Hz - 20kHz
Signal to Noise Ratio
Aux/Music Input: -90dB typically
Alert/Evac/Chime: -70dB typically
Input Sensitivity
Mic: 2mV Balanced
Aux Inputs: 300mV Unbalanced
Output Connectors
Audio Output: RCA Stereo Socket
Switched 24V DC Out: Screw Terminals
Input Connectors
Mic: 5 pin XLR
Aux Inputs: RCA Stereo Socket
24V DC Power: Screw Terminals
240V AC Power: IEC Chassis Socket
Remote Contacts: Screw Terminals
Muting: PTT Via Microphone
Switch Contacts
Controls
Mic Input: Rear Volume
BGM Input: Rear Volume
Aux Input: Front Volume
Tones & Chime: Rear Volume
Power: On/Off Switch
Mode Selection: 003 Keyswitch
Alert Switch: Illuminated Switch
Evac Switch: Illuminated Switch
Bell / Chime Switch: Illuminated Switch
Indicators: Power on LED
Power Supply: 240V AC or 24V DC
Current Draw: 50mA (idle), 130mA (max).
Dimensions: 483W x 152D x 44H
Protection: 1A Fuse
Weight: 2.5 kg
Colour: Black
Options: A 2076 Voice Over Module
* Specifications subject to change without notice.



Product Warranty


1 Year Return to Base
 


L7: 1 | TM: 0 | LM: 2 | TY: 5 | T: 1615